Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series
CVE-2021-35533
7.5HIGH
Summary
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
Affected Version(s)
RTU500 series CMU Firmware version 12.0 <= 12.0.*
RTU500 series CMU Firmware version 12.2 <= 12.2.*
RTU500 series CMU Firmware version 12.4 <= 12.4.*
References
CVSS V3.1
Score:
7.5
Severity:
HIGH
Confidentiality:
None
Integrity:
None
Availability:
None
Attack Vector:
Network
Attack Complexity:
Low
Privileges Required:
None
User Interaction:
None
Scope:
Unchanged
Timeline
Vulnerability published
Vulnerability Reserved