Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series
CVE-2022-28613
Key facts
CVE-2022-28613 is a high severity (CVSS 7.5) vulnerability in Hitachi RTU500 series CMU Firmware. No exploitation in the wild or public proof-of-concept has been recorded so far. Its EPSS score is 1.0%, the estimated probability of exploitation in the next 30 days.
How risky is it?
- Yes: Works over the network, no login needed
- No: No public exploit code yet
- No: No attacks seen yet
- No: Not on CISA's exploited list
Our verdict
Check today
Find out if you're affected. If you are, patch.
What to do
1Check the vendor's fix
No fixed version is recorded yet. The vendor advisory is the authoritative source for patches.
Read the vendor advisory ↗2Can't patch yet? Reduce exposure
It can be reached over the network, so limit who can reach Rtu500 Series Cmu Firmware. Block it from the internet, allow only trusted hosts or a VPN, and turn off the affected feature if you don't use it, until you can update.
3Why it's rated "Check today"
- It can be exploited remotely without credentials.
- Its CVSS severity is high (7.5).
What is CVE-2022-28613?
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
Affected Version(s)
RTU500 series CMU Firmware 12.0.*
RTU500 series CMU Firmware 12.2.*
RTU500 series CMU Firmware 12.4.*