A vulnerability exists in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected conne ...
CVE-2022-29492
Summary
Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:::::::* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:::::::* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:::::::*
Affected Version(s)
MicroSCADA Pro SYS600 <= 9.2 FP2 Hotfix 4
MicroSCADA X SYS600 10
MicroSCADA X SYS600 10.1
References
CVSS V3.1
Timeline
Vulnerability published
Vulnerability Reserved