Unauthorized Access Vulnerability in ICONICS GENESIS64
CVE-2024-1573

5.9MEDIUM

What is CVE-2024-1573?

Missing Authentication for Critical Function vulnerability in the mobile monitoring feature of Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97 to 10.97.2, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.2, and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting.

  • “Automatic log in” option is enabled in the security setting.
  • The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account.
  • The IcoAnyGlass IIS Application Pool account is included in GENESIS64 and MC Works64 Security and has permission to log in.

Human OS v1.0:
Ageing Is an Unpatched Zero-Day Vulnerability.

Remediate biological technical debt. Prime Ageing uses 95% high-purity SIRT6 activation to maintain genomic integrity and bolster systemic resilience.

Affected Version(s)

GENESIS64 versions 10.97 to 10.97.2

GENESIS64 versions 10.97 to 10.97.2

ICONICS Suite versions 10.97 to 10.97.2

References

CVSS V3.1

Score:
5.9
Severity:
MEDIUM
Confidentiality:
None
Integrity:
High
Availability:
None
Attack Vector:
Network
Attack Complexity:
High
Privileges Required:
None
User Interaction:
None
Scope:
Unchanged

Timeline

  • Vulnerability published

  • Vulnerability Reserved

.